This make furbace start and stop over and over





















This is the insidr of a coil. You are looking at a 1/4 inch of dirt. I scrapped a clean spot on the bottom to help you see. The air can not pass threw this . The furnace gets to hot and the flame goes out. It cools down about d relites in a minute. This can do this 40 times a day. It shortens the life of the unit. A cheap screen filter caused this. The filter was cleaned regularly but there was never any dirt on it. It was to cheap to stop the dirt. A house with return air grills on the floor needs the filters change more often. Add kids and pets and that filter will get clogged fast. Keep a clean filter. This cost $175 to clean. It was 15 years old and rusty in places so it was replaced. It was $900. Do not use the $15 filters fron the hardware stores. Theyblock to much air. A 90 day filter is trouble too. The $1 filters don’t stop anything. Stay in the $3-$5 range. A furnace will turn off and on right away if it doesn’t get enough air flow. A bad blower or bad board can do this too. The main cause us air flow by dirty coil ir dirty filter Aaac service heating and air 7708754113



Aaac service residential furnace and air conditioner repair.7708754113